Use cases

Use cases.

Seven decisions from peer-reviewed work on cooling, power and reliability in large-scale datacenters. Each is written as a decision, the key uncertainties, and what the optimiser returns. Results in quotation marks are from the abstracts. Research, not client work.

  1. UC 01Two-phase immersion (2PIC)
  2. UC 02Cooling technology selection
  3. UC 03Stranded redundant power
  4. UC 04Power oversubscription
  5. UC 05Cooling under-provisioning
  6. UC 06Environment and reliability
  7. UC 07Life-cycle impact of cooling

UC 01Two-phase immersion (2PIC)

Two-phase immersion cooling (2PIC): can boiling headroom raise density under fluid and containment risk?

High-power accelerators outrun air and push cold-plate loops toward their coolant limit. Two-phase immersion (2PIC) boils dielectric fluid directly on the die, turning thermal margin into a coupled supply, containment and reliability problem.

Decision

Air or cold plates, or two-phase immersion (2PIC) with tuned clocks, tank sealing and condenser sizing?

Key uncertainties

Dielectric fluid supply and PFAS regulatory exposure; vapour loss and top-up cost; boiling heat-transfer margin at high TDP; condenser and facility-water temperature; tank sealing and maintenance downtime; GPU/server compatibility and warranty.

What the optimiser returns Illustrative

Treat the paper’s 13% cost saving as an upper bound, not a certain point (P10 ≈ 1.3% if uniform on [0, 13%]). Size condenser coils and facility-water temperature for boiling margin at peak TDP, price fluid top-up, PFAS-substitution buffers and seal-maintenance windows into E[TCO] + λ·CVaR, and optimise capacity per MW (+20% packing density in the paper) under P[thermal excursion] ≤ ε.

“overclocking can improve performance by 20%, increase VM packing density by 20%, and improve tail latency in auto-scaling scenarios by 54%. The combination of 2PIC and overclocking can reduce platform cost by up to 13% compared to air cooling.”From the paper abstract. Jalili et al., Cost-Efficient Overclocking in Immersion-Cooled Datacenters, ISCA 2021 · Misra et al., IEEE Micro Top Picks, 2022 · Peterson et al., air removal in 2PIC, ASME InterPACK 2021
A TWO-PHASE IMMERSION TANK (SECTION)vapour ptank, Tsatpressure control (bellows, PRV)12TTCS,r (to CDU)TTCS,s (from CDU)condenser coilQcond = U·A·ΔTlmliquid level, freeboard hfserver blade (vertical)package, boiling surfaceboiling-enhancement coatingfluid at Tsat, ptankQIT = ṁ_v · hfgfiltration: carbon + aluminaTwo-phase containment: bellows pressure control, sealed lid,air removal and filtration keep vapour loss & top-up bounded.B CDU, FACILITY WATER, HEAT REJECTION12CDUplate HXqTCSTFWS,rTFWS,sqFWSdry coolerTambchiller trim (opt.)heat reuse (opt.)DESIGN RELATIONS (SYMBOLIC)QIT = qTCS · ρcp · (TTCS,r − TTCS,s)Tsat − TTCS,r ≥ ΔTcond (condensate film)TTCS,s − TFWS,s ≥ ΔTCDU (HX approach)TFWS,s − Tamb ≥ ΔTDC (else trim)QIT + Qpump = qFWS · ρcp · (TFWS,r − TFWS,s)Schematic; symbolic quantities only. Connectors 1, 2 join sheet A to sheet B.
A TWO-PHASE IMMERSION TANK (SECTION)vapour ptank, Tsatpressure control (bellows, PRV)12TTCS,r (to CDU)TTCS,s (from CDU)condenser coilQcond = U·A·ΔTlmliquid level, freeboard hfserver blade (vertical)package, boiling surfaceboiling-enhancement coatingfluid at Tsat, ptankQIT = ṁ_v · hfgfiltration: carbon + aluminaTwo-phase containment: bellows pressure control, sealed lid,air removal and filtration keep vapour loss & top-up bounded.B CDU, FACILITY WATER, HEAT REJECTION12CDUplate HXqTCSTFWS,rTFWS,sqFWSdry coolerTambchiller trim (opt.)heat reuse (opt.)DESIGN RELATIONS (SYMBOLIC)QIT = qTCS · ρcp · (TTCS,r − TTCS,s)Tsat − TTCS,r ≥ ΔTcond (condensate film)TTCS,s − TFWS,s ≥ ΔTCDU (HX approach)TFWS,s − Tamb ≥ ΔTDC (else trim)QIT + Qpump = qFWS · ρcp · (TFWS,r − TFWS,s)Connectors 1, 2 join sheet A to sheet B. Schematic.
Figure UC1Immersion cooling system architecture: two-phase tank (A); CDU, rack-side (TCS) and facility (FWS) loops, and heat rejection (B). Symbolic quantities only.

IllustratesT2Full optimisation study →Pillars 0103

UC 02Cooling technology selection

Air, cold plate or two-phase immersion for a high-heat-flux part?

Air throttles above a certain heat flux. Which liquid technology delivers the most sustained performance?

Decision

How warm can the facility water run for this part, and does that rule a technology in or out?

Key uncertainties

Junction-temperature margin, not peak TDP. The package resistance fixes how warm the coolant can run.

What the optimiser returns Illustrative

For a 200 W part, the paper’s best resistance of 0.247 °C/W puts the junction ≈ 49 K above the fluid. With Tj,max = 95 °C the fluid must stay below ≈ 46 °C before any approach temperature: the facility-water class follows from the package, and the technology is chosen on sustained clocks at that water temperature.

“higher CPU clock rates up to 41% utilizing cold plates and 51% employing 2P immersion … the least thermal resistance (as low as 0.247 °C/W)”From the paper abstract. Ramakrishnan et al., IEEE Trans. CPMT, 2021

IllustratesT3Ongoing scenario simulation →Pillars 0301

UC 03Stranded redundant power

Can redundant power be used without losing availability?

Redundant power and cooling sit idle except during failures, so utilisation is low and more sites get built.

Decision

Keep 2N reserve power idle, or deploy onto it with fast workload shedding?

Key uncertainties

The probability that a failure coincides with load above what can be shed in time, and the cost of shedding the wrong workloads.

What the optimiser returns Illustrative

On 30 MW of IT built 2N, the paper’s “up to 33% more servers” is roughly 10 MW of additional deployed IT on the same infrastructure. Deploy onto reserve only if E[shedding cost] across failure scenarios is below the cost of building that capacity, subject to P[critical workload shed] ≤ ε.

“Flex produces less than 5% stranded power and increases the number of deployed servers by up to 33%”From the paper abstract. Zhang et al., Flex: High-Availability Datacenters With Zero Reserved Power, ISCA 2021
A ELECTRICAL ONE-LINE (ONE PATH)utility, HVHV/MV transformerMV switchgearMV/LV transformerUPSBESSbuswayrack PSUIT load PIT(t)ωFωSωSωFωLB THERMAL LOOP (SAME RACK)ambient Tdb, Twbdry coolerchiller trimfacility waterTFWS,s / TFWS,rCDUTCS / fluid loopTsupply, qimmersion tankor cold platesQIT(t) = PIT(t)ωAωFωFωSC STOCHASTIC INPUTS → OPTIMIZERωLload PIT(t), growthωFfailures λk, MTTRkωAambient Tdb, TwbωSlead times LkJOINT OPTIMIZERminx Eω[TCO] + λ·CVaRαP[ Psite > Pgrid ] ≤ εPP[ Tsupply > TW ] ≤ εWP[ RFS > t* ] ≤ εSCOUPLED DECISIONS x· N+k per stage (A, B)· BESS energy E, power P· Tsupply, ΔT, flow q· dry cooler / trim split· cap policy on PIT(t)· order dates, second sourcePIT(t) is shared: every watt in sheet A leaves as heat in sheet B. Tags ω mark where each stochastic input enters. Schematic.
A ELECTRICAL ONE-LINE (ONE PATH)utility, HVHV/MV transformerMV switchgearMV/LV transformerUPSBESSbuswayrack PSUIT load PIT(t)ωFωSωSωFωLB THERMAL LOOP (SAME RACK)ambient Tdb, Twbdry coolerchiller trimfacility waterTFWS,s / TFWS,rCDUTCS / fluid loopTsupply, qimmersion tankor cold platesQIT(t) = PIT(t)ωAωFωFωSC STOCHASTIC INPUTS → OPTIMIZERωLload PIT(t), growthωFfailures λk, MTTRkωAambient Tdb, TwbωSlead times LkJOINT OPTIMIZERminx Eω[TCO] + λ·CVaRαP[ Psite > Pgrid ] ≤ εPP[ Tsupply > TW ] ≤ εWP[ RFS > t* ] ≤ εSCOUPLED DECISIONS x· N+k per stage (A, B)· BESS energy E, power P· Tsupply, ΔT, flow q· dry cooler / trim split· cap policy on PIT(t)· order dates, second sourceTags ω mark where each stochastic input enters.
Figure UC3Electrical path and thermal loop for the same IT load, with stochastic inputs ω feeding the optimizer. Schematic.

IllustratesT2Full optimisation study →Pillars 0102

UC 04Power oversubscription

How far can power be oversubscribed when the workloads are unknown?

Public clouds cannot see what runs inside VMs, so oversubscription is kept conservative.

Decision

How far to oversubscribe power when the workloads are opaque?

Key uncertainties

Capping a critical workload. Prediction error widens the tail, so the oversubscription limit is a chance constraint, not a fixed ratio.

What the optimiser returns Illustrative

If a hall runs 10% oversubscription today, the paper’s 2× increase takes it to 20%: on a 20 MW provisioned hall that is 2 MW of extra sellable capacity, accepted only while P[cap on critical] ≤ ε holds under the prediction-error distribution.

“we enable a 2x increase in oversubscription with minimum impact to critical workloads”From the paper abstract. Kumbhare et al., Prediction-Based Power Oversubscription in Cloud Platforms, USENIX ATC 2021

IllustratesT3Ongoing scenario simulation →Pillars 0102

UC 05Cooling under-provisioning

Do we need to provision cooling for the worst case?

Cooling is sized for peak load at peak outdoor temperature at the same time, a rare combination.

Decision

Size cooling for the coincident worst case, or for a stated percentile of the joint load–weather distribution?

Key uncertainties

Hours where load and outdoor conditions together exceed plant capacity, and what is throttled in those hours.

What the optimiser returns Illustrative

If the coincident peak is 10 MWth but the 99.9th percentile of hourly demand is 8.2 MWth, sizing to 8.2 removes 18% of plant capacity for an expected ~9 excursion-hours a year, handled by a defined throttling policy. The paper reports up to 55% lower cooling cost from this kind of provisioning.

“CoolProvision can reduce the cost of cooling by up to 55%”From the paper abstract. CoolProvision: Underprovisioning Datacenter Cooling, ACM SoCC 2015

IllustratesT1Fast risk scan →Pillars 0203

UC 06Environment and reliability

How much does free cooling cost in hardware failures?

Free cooling exposes servers to higher and more variable temperature and humidity. The reliability cost was unclear.

Decision

How wide a temperature and humidity envelope to allow for free cooling?

Key uncertainties

Component failures rise with relative humidity more than with temperature; the energy saving is near-certain, the failure cost is uncertain.

What the optimiser returns Illustrative

Choose RHmax to minimise E[energy cost] + E[failures(T, RH)] · crepair, with failures from a field-fitted hazard model rather than a vendor limit. The paper found the infrastructure and energy savings “far outweigh” the extra failures.

“relative humidity seems to have a dominant impact on component failures … resulting in significantly lower infrastructure and energy costs that far outweigh the cost of the extra component failures”From the paper abstract. Environmental Conditions and Disk Reliability in Free-Cooled Datacenters, USENIX FAST 2016

IllustratesT1Fast risk scan →Pillars 0203

UC 07Life-cycle impact of cooling

Which cooling technology is more sustainable across its full life cycle?

Cooling choices are usually judged on PUE alone, which misses embodied carbon and water.

Decision

Which cooling technology, judged over its full life cycle rather than PUE?

Key uncertainties

Ranges, not points: the paper reports 31–52% lower blue water and 15–21% lower GHG for cold plates and immersion vs air.

What the optimiser returns Illustrative

A water-capped site should plan on the low end of the range (31% less blue water) and treat the rest as upside. Carbon and water then enter the objective next to cost, under the same scenarios.

“cold plates and immersion cooling, in reducing greenhouse gas emissions (15–21%), energy demand (15–20%) and blue water consumption (31–52%)”From the paper abstract. Alissa et al., Using life cycle assessment to drive innovation for sustainable cool clouds, Nature, 2025

IllustratesT2Full optimisation study →Pillars 0304